The EverExceed uXcelPremium® industrial battery charger is the flagship charger of EverExceed Industrial Power solutions. It integrates proven design topology with the latest advanced digital control technology to control the 12-pulse thyristor bridge rectifier and provide the most reliable and trouble-free performances in any electrical and industrial environments. EverExceed uXcel® range rectifier chargers can continuously protect your critical DC power industrial equipments and operations from the damage of power failures and interruptions, with its high reliability and superior performance.
- Lead Time:Normally 4~6 weeks
- Brand:EverExceed
- Nominal DC Voltage(Output):24/48/110/125/220/240/400V
- Nominal DC Current(Output):10-1500A
- Input AC Voltage:Single phase 1×230V(220,240)/Three phase 3×400V(380,415)other input voltage can be customized
- Battery Type:Lead acid batteries, nickle cadmium batteries, lithium batteries
- Communication:RS232/RS485 Modbus, TCP/IP Ethernet (optional)
- OEM/ODM Service:Yes, customized service available
- Certificates:CE, EN61000, IEC60146
Technical features
|
|
|
Large LCD display
|
Leading Technology
|
High Reliability and High MTBF |
User friendly operation with large LCD display, optional touch screen with the choices of 8 languages ensure easy maintenance and operation. Smart communication and remote monitoring. |
The embedded micro-computer controller processes signals 10 times faster than standard analog methods. |
Fully automatic battery management with “four remote”
functions meeting requirements of untended duty control.
|
|
|
|
Isolation transformer
|
Flexible maintenance and Reduced MTTR
|
Long design life up to 20+years |
Filter more than 3 harmonics in the power grid interference to the system equipment, while strengthening the operation security of the system.
|
The design make it easy for front-access to all vital modules modules of the charger
Versatile constant voltage and constant current charging modes
Smart communication and Remote Monitoring through isolated RS232, RS485, Ethernet. Full data logging. |
System design life up to 20+ years in continuous operation under the condition of appropriate maintenance. |
|
|
|
Flexibly customized
|
Ruggedized solutions
|
Complete power protection solutions |
Power solutions to perfectly meet the specific requirements of customer’s industrial applications.
|
To withstand harsh environments,extreme temperatures, humidity, dust and vibrations etc. Up to IP55 protection. |
Including switchgear,DC distribution, monitoring suite. |
|
AC voltage |
3×400V(380,415) |
Three phase |
Input voltage tolerance |
±10% |
Input wiring |
3 Phase 3 Wirse or 3 Phase 4 Wires |
Input frequecny |
50Hz(60Hz) |
Input frequecny tolerance |
±5% |
Input protection |
Thermic Magnetic Overcurrent protection via MCCB |
Input power factor |
>0.9 |
Input THDi |
10%~15% |
OPTIONS |
Rectifier |
Other input voltage |
Blocking diode |
Surge and Lightning protections |
Voltage ripple filter |
Battery circuit protection box |
Bettery |
Battery reversed polarity detection |
Battery low-voltage disconnection contactor (LVD) |
Battery room temperature sensor |
Battery cabinet / rack |
Battery monitoring system |
Parallel configurations |
System |
Dropping diodes/DC-DC converter |
Earth fault monitoring |
Internal cabinet lighting |
Anti-condensation heater |
Output breaker |
Front-panel analog meters/digtal meters |
DC distribution |
Temparature compensation |
AC high and AC low alarm/protection |
DC high and DC low alarm/protection |
AC fault alarm |
LED test function |
Other frame colour |
Mechanical |
Up to IP55 external |
Plate thickness |
Gaivanized sheet |
Front access maintenance |
Top cable entey |
Specified cabinet identification(tag,nameplate) |
Communication |
Modbus TCP/IP |
DNP3.0 protocol |
Volt-free contacts |
Transducers 4-20mA |
|
|
|
|
OUTPUT |
Nominal DC voltage |
24/48/110/125/220/240/400 |
Output voltage range |
0-1.5×nominal voltage (adjustable) |
Nominal DC current |
10-1500A |
Output current range |
0-1.1×nominal current(adjustable) |
Voltage stability |
±1% in float mode, input within tolerance |
Voltage ripple |
1% RMS(with battery connected) |
Current Limitation |
Battery current limitation can be adjusted |
Filtering |
L-C Filter |
Output Protection |
Short Circuit, NH Fuse and Overvoltage protection |
BATTERY |
Type |
Lead acid or nickel cadmium,
vented or recombination and Lithium battery |
COMMUNICATION |
Communication |
RS232, Modbus RTU |
GENERAL DATA |
Operating temperature |
0 to 50 °C |
Storage temperature |
-20 to +70 °C |
Relative humidity |
< 95 % non condensing |
Operating altitude |
1000 m max without derating |
Cooling |
Fan cooling or Natural cooling according to rating |
Efficiency |
90% according to rating |
External protection |
IP20 |
Noise
(at 1m in front of the unit) |
55 – 65 dB according to rating |
Cabinet color |
RAL 7035 |
Dimensions |
Varying according to ratings & options |
STANDARDS |
IEC60146-1-1:2009 |
Semiconductor converters –
Specification of basic requirements |
IEC62040-1:2008+AMD1:2013 |
Uninterruptible power systems (UPS)
– Part 1-2: General and safety requirements
for UPS in restricted access locations |
IEC62040-2:2006 |
Uninterruptible power systems (UPS) – Part 2:
Electromagnetic compatibility (EMC) requirements |
IEC61439-1:2011 |
Low voltage switchgear and controlgear assemblies –
Part 1: General rules |
IEC60529:1989+
AMD1:1999 |
Degrees of protection provided by enclosures (IP Code) |
IEC60076-11:2004 |
Power transformers – Part 11: Dry type transformers |
European Directives |
Low voltage directive: 2006/95/EC and 2014/35/EU
EMC directive: 2004/108/EC and 2014/30/EU
CE Mark |
|