Technical features:
>Wide input AC voltage range: 90~290 Vac; | >Provide 6 sets of passive dry contacts; | >Power factor values up to 0.99; | ||
>With battery management system, with battery temperature probe; | >Standard 19-inch 2U frame for easy cabinet installation; | >With activity alarm, sound and light form to remind alarm information; | ||
>Have rich LED+LCD status display, alarm signal display and alarm recording functions; | >Ultra-lowradiation: using adyanced electromagnetic compatibility design; | >Efficiency of the whole machine: 93.2%; | ||
>48V single module output current 50A/30A optional, 24V single module output current 60A, 2U system output current up to 150A, overall current up to 600A; | >Temperature compensation system, which can be set to protect once power off and two times power off; | >The system configuration is flexible, convenient and easy to expand. Various power systems can be configured according to the customer needs; |
System Schematic:
Applications:
Widely used in communication and industrial fields. All of its communication power technology converts alternating current to direct current to supply power to the DC load, connects the battery pack in the power system to charge the battery pack, and detects the battery pack status. Three hot-swappable rectifier module ports can form an N+1 redundant system to provide fault tolerance for the load. In order to adapt to different external power supply systems, the monitoring system is equipped with 45 different alarm options. The monitoring screen can display current alarm information, query historical alarm information, and support RS485/SNMP remote operation.
Model | ER4830 | ER4850 | ER2460 | |
AC input | Voltage | Single phase 220Vac/110Vac | ||
frequency | 50/60Hz (45-66Hz) | |||
voltage range | 90-290Vac | |||
DC Output | Rated voltage | 48VDC | 24VDC | |
float voltage | 53.5VDC (42-58V) | 26.7VDC (21-29V) | ||
Equalizing voltage | 56.4VDC (42-58V) | 28.2VDC (21-29V) | ||
power factor | >0.99@220VAC | |||
efficient | >92%@220VAC peak: >93.2%@220VAC 100% load | |||
output precision | ≤0.6% | |||
leakage current | <10mA | |||
Output current | 30A | 50A | 60A | |
RS485 | Default (Modus RTU) | |||
Communication | TCP/IP | default | ||
Interface | SNMP card | Optional | ||
dry contact | 6 groups of DI, 6 groups of DO | |||
LCD display | Input/output voltage, frequency, output current, ambient temperature, load | |||
Instruction | power state | Mains/Output/Undervoltage@Voltage Overload | ||
Isolation voltage | Input – Output | RMS 3000Vac 50Hz or equivalent 4240VDC 1 minute ≤ 1mA | ||
Input – Chassis | RMS 1500Vac 50Hz or equivalent 2120VDC 1 minute ≤ 1mA | |||
Output – Chassis | RMS 500Vac 50Hz or equivalent 710VDC 1 minute ≤ 1mA | |||
Insulation resistance | @Normal atmospheric pressure, 90% relative humidity Test voltage input-output, input-ground DC isolation 500V Output-ground shall not be less than 10MΩ | |||
Fan speed | Temperature and Output Current Regulation | |||
Operating temperature | -40 +55°C (-40 +135°F) | |||
Temporary storage | -40 +70°C (-40 +158°F) | |||
High | working height |
0~4000 meters, based on 3000 meters,
the temperature drops by 1℃ for every 200 meters above sea level
|
||
Storage height |
0~4000 meters, based on 3000 meters,
the temperature drops by 1℃ for every 200 meters above sea level
|
|||
Noise | <55dB at nominal input and full load (ambient temperature <30℃) | |||
Cool down | Fan (front and rear airflow) | |||