Brand | |
---|---|
Customer Application |
Airports |
Customer Type |
Airports |
Brand | |
---|---|
Customer Application |
Airports |
Customer Type |
Airports |
EverExceed Modular Max Range Valve Regulated Lead Acid (V.R.L.A.) batteries are designed for the long standby back-up power requirements of wireless / PCS telecommunications, MTSOs, central offices, utilities, switchgear and control applications. Our advanced AGM absorbed electrolyte technology coupled with thick positive plates and a welded / epoxy, dual post seal ensures reliable performance, safety, outstanding battery life and value.
Technical Features:
![]() |
![]() |
![]() |
||
Superior cycle performance | Unique performance | VRLA recombinant technology | ||
Thick plate design for extra long cycle life. Nano-carbon enhanced active material to maximize cycle performance and PSoC operation |
Proprietary Fixed Orifice Plate Pasting technology applying active materials on both sides of the grid for consistent cell-to-cell performance, higher capacity and uniform grid protection.
|
High-Compression Absorbed Glass Mat technology (AGM) for greater than 99% recombination efficiency. | ||
![]() |
![]() |
![]() |
||
Wide operating temperature range | Ultra long backup time | Long service life | ||
-40°C to +70°C Storage time from a fully charged condition: 12 months at 20°C ~25°C ; for each 9°C rise, reduce the storage time by half. |
Fully tank formed plates design which is perfectly suitable for long standby backup power requirements. | Thick positive plate design for maximum service float life- 20 years design life @ 20°C(68°F). | ||
![]() |
![]() |
![]() |
||
Assured quality
|
Maintenece free | Low self-discharge rate | ||
These industry leading rechargeable batteries are approved with UL1989, CE, IEC60896, IEC61427 | No maintenance required, never needs addition of water. | Less than 3% per month |
![]() |
① Positive plate – Thick 0.245″(6.2mm) lead-calcium-tin grids minimize corrosion and prolong life. |
Applications: |
• Telecommunications ; • Emergency Lighting ; • Navigation Aids ; • UPS system; • Switchgear ; • Communications ; • Grid scale energy storage ;
• Cellular Radio; • Control Systems; • Standby Power Supply; • Photovoltaic / Solar; • Remote/Hybrid Sites; • Off-Grid/Renewable; • Other cycling applications
Model No. | Nominal Voltage (V) | Nominal Ah Cap. @10hr to 1.80VPC | Outline dimensions (mm/inch) | Weight | Terminal Type | No. of Terminal | Internal Resist mOhms | Max. Charge Current (A) | Short Circuit Current (A) | ||||||||
Length | Width | Height | Total Height | ||||||||||||||
mm | inch | mm | inch | mm | inch | mm | inch | kg | lbs | ||||||||
MR 2-200 Max | 2 | 200 | 90 | 3.54 | 181 | 7.13 | 346 | 13.6 | 365 | 14.4 | 12.5 | 27.5 | F-M8 | 2 | 0.6 | 40 | 1620 |
MR 2-300 Max | 2 | 300 | 124 | 4.88 | 181 | 7.13 | 346 | 13.6 | 365 | 14.4 | 17.5 | 38.5 | F-M8 | 2 | 0.5 | 60 | 2410 |
MR 2-400 Max | 2 | 400 | 158 | 6.22 | 181 | 7.13 | 346 | 13.6 | 365 | 14.4 | 23 | 50.6 | F-M8 | 2 | 0.4 | 80 | 3220 |
MR 2-500 Max | 2 | 500 | 191 | 7.52 | 181 | 7.13 | 346 | 13.6 | 365 | 14.4 | 28 | 61.6 | F-M8 | 2 | 0.35 | 100 | 4100 |
MR 2-600 Max | 2 | 600 | 225 | 8.86 | 181 | 7.13 | 346 | 13.6 | 365 | 14.4 | 33 | 72.6 | F-M8 | 2 | 0.3 | 120 | 4860 |
MR 2-800 Max | 2 | 800 | 303 | 11.9 | 181 | 7.13 | 346 | 13.6 | 365 | 14.4 | 45 | 99 | F-M8 | 4 | 0.29 | 160 | 6400 |
MR 2-1000 Max | 2 | 1000 | 370 | 14.6 | 181 | 7.13 | 346 | 13.6 | 365 | 14.4 | 55 | 121 | F-M8 | 4 | 0.26 | 200 | 7900 |
MR 2-1500 Max | 2 | 1500 | 551 | 21.7 | 181 | 7.13 | 369 | 14.5 | 388 | 15.3 | 85.5 | 188 | F-M8 | 8 | 0.2 | 300 | 12500 |
MR 2-2000 Max | 2 | 2000 | 385 | 15.2 | 363 | 14.3 | 369 | 14.5 | 388 | 15.3 | 114 | 250 | F-M8 | 8 | 0.15 | 400 | 16200 |
MR 2-3000 Max | 2 | 3000 | 568 | 22.4 | 363 | 14.3 | 369 | 14.5 | 388 | 15.3 | 172 | 378 | F-M8 | 12 | 0.12 | 600 | 24200 |