| Brand | |
|---|---|
| Customer Application |
Airports |
| Customer Type |
Airports |
| Brand | |
|---|---|
| Customer Application |
Airports |
| Customer Type |
Airports |
Technical features
Custom Dual-System Design
The chargers feature two independent systems in one cabinet, with outputs of 220V 60A and 24V 60A. |
Dual Isolation Transformers
Dual isolation transformers for voltage conversion and isolation. |
Voltage Adaptation
One system charges 105 batteries, the other 12, with power selectable from either charger or total voltage to meet varying voltage needs. |
In Series Connection
The master unit runs under normal conditions, and the slave unit takes over in case of a fault. Once the fault is resolved, both units can operate together or independently. |
Modbus & Dry Contact Functionality
Supports Modbus TCP/IP communication and dry contact function, making it easy to connect with the customer’s system. |
Touch Screen Control
Customers can monitor charging status and real-time alarms via a touch screen. |
| GENERAL | |
| Model | uXcel ultra -220V80A/16V60A |
| Topology | 6 pulse full bridge thyristor rectifier |
| Control | Microprocessor controlled system |
| Standars | IEC60146、IEC60439、IEC60725、IEC61000-6-2、IEC61000-6-4、IEC62040(-1,-2,-3) |
| Configuration | Parallel(One work, one standby) |
| ENVIRONMENT | |
| Operation temperature | 0 – 50℃ |
| Storage temperature | -20 to +70℃ |
| Relative humidity | < 95% ( no condensation of moisture ) |
| Altitude | 1000 m Max without derating |
| INPUT PARAMETERS | |
| Input isolation transformer | Galvanically isolated / Primary & Secondary earth screened |
| AC voltage and tolerance | 380VAC±10%, three-phase |
| Input frequency and tolerance | 50Hz/60Hz ±5% |
| Input protection | Input MCCB Thermic magnetic overcurrent protection,AC SPD |
| OUTPUT PARAMETERS | |
| Nominal output voltage | 220VDC/16VDC |
| Float voltage | 0-300V/0-24V adjustable |
| Boost voltage | 0-300V/0-24V adjustable |
| Voltage stability | ±1% in float mode, input within tolernce |
| Nominal output current | 80/60A |
| Output current adjustment | 0‐100% of Nominal Output Current |
| Output ripple | 1% RMS (with battery connected) |
| Mode of operation | constant voltage/constant current |
| Static voltage regulation | < 1% |
| Efficency | 88% |
| Filter | L-C Filter |
| Output breaker | DC1 battery MCCB,DC1 load MCCB,DC2 battery MCCB,Total load MCCB |
| Battery bank | Lead Acid or Nickel Cadmium vented or recombination |
| Boost voltage (V/C) | 2,35 lead acid battery 1,60 NiCd Battery (Depends on battery manufacturer recommendation) |
| Float voltage (V/C) | 2,25 lead acid battery 1,40 NiCd battery (Depends on battery manufacturer recommendation) |
| MECHANICAL PARAMETERS | |
| External protection | IP20, Cold rolled sheet |
| Panel thickness | Load Bearing: 2 mm, Non Load Bearing: 1.5 mm |
| Frame Colour | RAL7035 |
| Noise(dB ) | <50 dB |
| Cooling | Fan cooling |
| Cable Entry | Bottom |
| Dimensions | 1600H*1200W*800D(mm) |
| DISPLAY PANEL & MEASUREMENT | |
| Meter | DC1 voltage, DC2 voltage,Total voltage,DC1 current,DC1 current |
| Protection | Charger fault protection (DC overvoltage, DC overcurrent, Over temperature) |
| Alarm | Charger1 fault protection,Charger2 fault protection,BAT over temperature, Mains fault,DC1 overvoltage,DC1 undervoltage,DC2 overvoltage,DC2 undervoltage |
| Indication | LED lamp |
| Display | LCD display |
| OTHER FUNCTIONS | |
| Other funtions | |
| Battery temperature compensation | 3mV/cell, adjustable |
| Language | Customized |
| COMMUNICATION | |
| Communication | RS485, Modbus RTU |
| Dry contact | Charger fault |