Brand | |
---|---|
Customer Application |
Airports |
Customer Type |
Airports |
Brand | |
---|---|
Customer Application |
Airports |
Customer Type |
Airports |
Technical features
![]() |
![]() |
![]() |
High reliability |
Multi-stage protection |
Wide range of voltage |
Using high-frequency switching technology, modular design, N + 1 hot backup ensure high reliability. | Reliable and highly insulated protection measures to ensure that systems and personal safety. | Offers wide input voltage range from
90VAC~264VAC , which is suitable for different application scenarios. |
![]() |
![]() |
![]() |
Smart battery management |
All-in-one solution |
Friendly communication interfaces |
Fully automatic battery management with “four remote”
functions meeting requirements of untended duty control.
|
Integrated design configured with different modules (monitoring, rectifier, battery inspection, switch & insulation monitoring & buck module etc.) |
Provides RS232/RS485/Ethernet communication and MODBUS/IEC61850/DNP3.0/TCPIP communication protocol. |
![]() |
![]() |
![]() |
Smart remote monitoring |
Advanced technology |
Smart LCD display |
Online detection of battery voltage, temperature and internal resistance to eliminate
potential safety problem.
|
Charging module using the latest soft-switching
technology, high conversion effciency, low
electromagnetic interference.
|
Provides user-friendly large-screen graphic LCD display
with touch screen which is easy to operate. |
System application
Integrated DC and AC uninterruptible power supply system composed of key components
Items | 220V Series | 110V Series | 48V Series | 24V Series | |
Input | Input mode | Single phase L/N/PE or 3phase 4wires | |||
Input voltage | 90~264VAC or 380VAC±15% |
90VAC-290VAC or
90VDC-370VDC
|
90VAC to 290VAC
(nominal 176VAC~290VAC)
|
||
Frequency | 45Hz~65Hz | ||||
Power factor | ≥0.9 | ≥0.99@220VAC/50A | ≥0.99@220VAC/60A | ||
Output | DC distribution | According to actual situation | |||
Voltage range | 198VDC~286VDC adjustable | 99~143VDC adjustable | 43VDC-58VDC adjustable | 21VDC~29VDC adjustable | |
Voltage ripple | ≤+0.1% | ||||
Voltage regulation accuracy | ≤+0.5% | ||||
Current regulation accuracy | ≤+0.5% | ||||
Charging modules output | ≤5% | ||||
Current imbalance parameters | |||||
Efficiency | ≥0.93 (full load) |
≥92%@220VAC 50%-100% Load、
≥93%@peak value
|
>90%@220VAC@ 220VAC 100% load | ||
Insulating property | Output to ground | 2kVac,Leakage currents ≤30mA, 1 min, no electric arcing | |||
Input to ground | |||||
Input to output | |||||
System | Operation temperature | -10~+45℃ 100% power output | |||
+45~+ 60℃, power derated output | |||||
Storage temperature | -25°C- 70°C (without batteries) | ||||
Noise | ≤55dB | ||||
Mechanical parameter | Dimension (W*D*H) | 800mm*600mm*2260mm | |||
600mm*600mm*1600mm | |||||
Weight | 180-250kg (depend on system confguration) |