Additional information
Brand
Customer ApplicationAirports
Customer TypeAirports
Description

The STS uses thyristor module (SCR) as switching device to realize power-free switching between different input power supplies. It is used in the field of demanding high-end uninterruptible power supply( such as computer rooms, Internet data centers, telecommunications, financial data centers, industrial process control centers, etc).

Technical Features

Adopt 32-bit DSP full digital control technology,

with the feature of strong anti-interference,

 fast computing speed, high control accuracy,etc. Switching time ≤4ms.

Dual AC power switch, key equipment redundant power supply.

Advanced power failure detection method can quickly determine power failure.

LED indicator + LCD display monitor;

control screen (optional),

can monitor status information at any time.

         With overheating, overvoltage, overfrequency,

                 output overcurrent, overload and

                      other protection functions.

Independent RS485 communication interface supports real-time communication.

 

Specification 16A 25A 32A 40A 45A 63A 80A 100A 125A 63A
Capacity 3.5KVA 6.2KVA 7.7KVA 10KVA 11KVA 15KVA 19KVA 24KVA 27.5KVA 45KVA
Phase Single phase Three-phase
AC Input
AC Input Voltage 220Vac (customizable)
Ua=220Vac;
Ub=220Vac;
Uc=220Vac;
Input Voltage Range 190-260Vac 320-440Vac
Automatic Switching of Threshold Voltage 220Vac±15%; 380Vac±12.5%; hysteresis error of instrument ±5V 320-440Vac
Over Limit Protection Shutdown Threshold Voltage ≤165Vac @ ≥260Vac,  hysteresis error of instrument ±5V
Overrun Protection Shutdown Threshold Frequency ≤45Hz & ≥65Hz, hysteresis error of instrument±0.2Hz ≤42.5Hz or ≥57.5Hz,hysteresis error of instrument±0.2Hz
Automatic Switching of Threshold Frequency 50Hz±10%,hysteresis error of instrument±0.2Hz
Frequency 50Hz(±10%)
Overload Capacity
Load current ≤110%, continuou operation;
Load current>110%, shut down immediately;
Load current<105%, continuou operation;
Load current>105%, shutdown after 60ms;
Protection Function Input under-voltage and over-voltage protection, output overload protection, over-temperature protection, short circuit protection;
Switching Parameter
Priority Switch ≤4ms ≤8ms
Switching Poles Single-pole firewire switching (option: bipolar zero firewire switching)
Switching Element Thyristor Controlled (SCR)contactless switching
Switching Mode Break before Make
Switching Condition Power failure or overvoltage or undervoltage
Working Environment
Insulation Strength 2000Vac/10mA/60s
Humidity 0%~ 90%, no condensation
Operating Temperature -10℃~50℃
Storage Temperature -40℃~70℃
Noise (1m) <55dB
Dimensions (mm) 490*343*44(1U) 490*338*88(2U) 490*412*132(3U)
LCD Display (optional) Voltage, frequency, current, load percentage, etc. (LCD model)
Communications Interface RS485