Brand | |
---|---|
Customer Application |
Airports |
Customer Type |
Airports |
Brand | |
---|---|
Customer Application |
Airports |
Customer Type |
Airports |
PL31 RM series power supply adopts online double conversion design and digital control technology and it features high input and output power factor, self-adaptive output frequency according to input frequency, intelligent battery management and excellent network management.
Technical features
![]() |
![]() |
![]() |
Advanced technology | Smart charging | High efficiency |
True online double conversion technology | Automatic battery charging on/off mode | Advanced PFC technology and input PF >99% |
![]() |
![]() |
![]() |
Battery cold start | Complete Protection function | Superior reliability |
UPS can be powered on from the battery without utility. It will add great value to your workflow by providing on-demand power | Lighting & surge protection | Wide input voltage range enables it to be compatible with more operation environment |
Applications:
IDC( Inte rnet Dater Center), network,servers and workstations, control system, communication system,office,PC etc.
MODEL | PL31 RM10KL | PL31 RM15KL | PL31 RM20KL |
Capacity | 10kVA/10kW | 15kVA/15kW | 20kVA/20kW |
Phase | 3-Phase in/1 Phase out | ||
INPUT | |||
Nominal Voltage | 380/400/415Vac (L-L voltage), 3Ph+N+PE | ||
Input Voltage Range | 190~520Vac (L-L voltage) | ||
Input Frequency Range | 50/60±6Hz | ||
Input Power Factor | >0.99 | ||
Input Current Distortion (THDi) | ≤5% | ||
Bypass Voltage Range | -40%~20% of nominal voltage, adjustable | ||
OUTPUT | |||
Nominal Votage | 208/220/230/240Vac, L+N+PE | ||
Voltage Regulation | ± 1 % | ||
Nominal Frequency | 50/60Hz, adjustable | ||
Output Frequency | Line mode:50/60±1/2/3/4/5Hz, adjustable; battery mode: 50/60±0.01 Hz | ||
Output Power Factor | 1 | ||
Voltage Distortion (THDu) | ≤2%@linear load; ≤5%@non-linear load | ||
Transfer Time |
Line mode to Battery mode, 0ms; Inverter to Bypass, 0ms (Synchronized); Bypass to Inverter,
0ms(Synchronized); ECO to Battery Mode, 2ms (Typical Time)
|
||
Crest Ratio | 3:1 | ||
Overload Capacity (Normal Mode) |
30 min @ 102%~110% load;
10 min @ 110%~130% load;
30s @130%~150% load;
500 ms @ >150% load
|
||
Overload Capacity (Battery Mode) |
10 min @ 102%~110% load;
1 min @ 110%~130% load;
10s @130%~150% load;
500 ms @ >150% load
|
||
Output Short Circuit Protection | Line Mode: Current limitation; Battery Mode: Current limitation; Bypass Mode: Breaker | ||
BATTERY | |||
Battery Type | Sealed lead acid maintanance free | ||
Nominal Voltage | 192~240Vdc, adjustable | ||
Charging Voltage | Floating Charge, 2.25V/cell; Boost Charge, 2.35V/cell | ||
Battery Number&Capacity | External | ||
Charging Current | 1~12A, adjustable | ||
Charging Mode | Two Satges (CC/Floating) or Three Stages (CC/CV/Floating, adjustable) | ||
Typical Recharge Time | Depending on the capacity of external batteries | ||
Battery Protection |
Battery Leakage<500µA, Over Voltage Protection, Under Voltage Protection,
Over Current Protection; Battery Deep Discharge Protection
|
||
EFFICIENCY | |||
Line Mode | 94% (Max) | ||
Battery Mode | 92% (Max) | ||
ECO Mode | 98% (Max) | ||
INDICATORS | |||
LCD Panel | UPS status, Battery Level, Load Level, Input/Outpt/Battery Voltage, Fault&Alarm Code | ||
Audible Alarm | Utility Failure, Battery Voltage Low, Overload, System Fault | ||
MANAGEMENT | |||
Interface | RS232, USB, Parallel Card, EPO Port, SNMP Card (Optional), Relay Card (Optional) | ||
ENVIRONMENT | |||
Operating Temperature | 0~40 ℃ | ||
Operating Humidity | 0~95% RH, non-condensing | ||
Storage Temperature | -15~60℃ (Battery: 0-40 ℃) | ||
Altitude | <1000m, derating 1% per 100m from 1000 ~ 2000m | ||
Noise (1Meter away) | <60dB | ||
PHYSICAL | |||
Dimension(W*D*H, unit:mm) | 440*651*173 | ||
Net Weight (kg) | 35 | 36 | 37 |
Color | Black ( RAL9004) | ||
STANDARDS | |||
Safety | IEC 62040-1:2017 | ||
EMC | IEC 62040-2:2018 | ||
Performance | IEC 62040-3:2011 | ||
Battery | IEC 60896-22:2004 |