Product Features
![]() |
![]() |
![]() |
||
Safer | Smarter | Simpler | ||
● Reliable, resulting in improved uptime and lower maintenance costs;
● Enhanced support with a dedicated team of experts to assist;
|
● Increased intelligence with 24×7 remote and on-site monitoring, providing real-time visibility and immediate detection of anomalies;
● Smart lithium, lead-acid and lithium batteries can be used together in power systems, reducing CAPEX; |
● Simple design, factory pre-installed to minimize installation costs and time;
● Minimize expensive energy consumption;
● Module design, minimize initial investment, and flexible expansion; |
Benefit
Compatible with multiple battery types;
Built-in rectifier with up to 96% conversion efficiency; Advanced MPPT technology with a conversion efficiency of up to 97%; Complete protection functions ensure stable operation of the system; Reliable common positive electrode grounding provides stable -48VDC power supply; |
Plug and play, user-friendly operation;
IP55 protection level, outdoor installation; Highly customized, can be designed according to technical requirements. Optional 4G remote monitoring, APP/Website monitoring 24/7 uninterrupted power supply; Excellent heat dissipation method, forced cooling by fan, and insulation cotton to prevent heat radiation; |
The structures
Work Mode
Application
Base stations and wireless communication facilities; Electricity security system; Long-distance lines of communication; Emergency communications systems
MPPT Module | ECM48-50V2 |
MPPT input voltage range | 100~400VDC(derate@100-200VDC input) |
Max input current | 19A |
Max PV array power | 3000W |
Nominal output voltage | 48VDC |
Adiustable range of output voltage | 42~58VDC |
Rated output current | 55A @54.5VDC |
Maximum output current limitation | 57A |
Output regulation | ±0.5% |
Load sharing (min/max) | ±0.5% |
Efficiency | ≥96% |
Operating temperature range | ﹣40℃ to +75℃ |
Max number of parallel units | 20pcs |
Rectifier Module | ERC48-50V2 |
Input voltage range | 90~300VAC(derate@90~176VAC) |
Input frequency | 45Hz~66Hz |
Peak eficiency | 96% |
Power factor | 0.99 @100%load |
Rated power | 3000W |
Nominal output voltage | 48VDC |
Adiustable range of output voltage | 42~58VDC |
Rated output current | 56.1A @53.5VDC |
Maximum output current limitation | 62.5A |
Load sharing (min/max) | ±0.5% |
Max number of parallel units | 20pcs |
Distribution(customized) | |
Breaker | AC input MCB, Phostvoltaic input MCB, DC output MCB (LLVD+BLVD), Battery MCB |
Surge protection | AC SPD, DC SPD, Photovoltaic SPD |
Monitor Module | |
Monitoring |
Can monitor and control: rectifier module,
MPPT module and distribution parameters
|
Signal input |
2-way analog signal input (Battery and environment temperature);
2-way dry contact input
|
Signal output | 4-way dry contact output |
Communication port | RS485/SNMP |
Event log | Up to 1,000 historical alarm records |
General Data | |
External proteciton | IP20 (Up to IP65) |
Humidity | <95% |
Operating temperature | ﹣10℃ to +45℃ |
Storage temperature | ﹣25℃ to +70℃ (excluding batteries) |
Altitude | 2000m Max without derating |
Cooling | Fan cooling (air-condition optional) |
Cabinet color | RAL7035 |
Dimensions | Varying according to ratings and options |
Optional | |
Inverter | 1-6kVA, 48VDC/220VAC |
Battery | Lithium battery, Sealed Lead Acid AGM or GEL |
Dynamic environmental monitoring |
monitoring all parameters in cabinet (including battery, aricondition, inverter, rectifier, MPPT, distribution,and environment sensor);
Centralized monitoring of multiple sites
|