uXcel Series Industrial Battery Charger – Series Configuration
SKU:
uXcel Series Industrial Battery Charger - Series Configuration
Category: All Products
Tags: battery, Charger, Industrial, Series, Series Configuration, uXcel®
Additional information
| Brand | EverExceed |
|---|---|
| Customer Application | Airports |
| Customer Type | Airports |
Description
The 220V 80A & 16V 60A uXcel Industrial Battery Chargers are engineered to deliver reliable power for high-voltage switch operations, relay protection, accident lighting, and other critical systems. Designed to meet the operational requirements of both high-voltage and low-voltage distribution networks, the chargers ensure the stability of essential systems and alarm functions. This solution optimizes the power infrastructure, contributing to enhanced energy security, stable electricity supply, and sustainable economic and social development.
- Brand:EverExceed
- Input AC Voltage:380VAC 60HZ
- Battery Type:Lead acid batteries
- Communication:Mobus TCP/IP
- OEM/ODM Service:Yes, customized service available
- Certificates:CE, EN61000, IEC60146
- Output Current:80A/60A
- Output Voltage:220VDC/16VDC
Technical features
Custom Dual-System Design
The chargers feature two independent systems in one cabinet, with outputs of 220V 60A and 24V 60A. |
Dual Isolation Transformers
Dual isolation transformers for voltage conversion and isolation. |
Voltage Adaptation
One system charges 105 batteries, the other 12, with power selectable from either charger or total voltage to meet varying voltage needs. |
In Series Connection
The master unit runs under normal conditions, and the slave unit takes over in case of a fault. Once the fault is resolved, both units can operate together or independently. |
Modbus & Dry Contact Functionality
Supports Modbus TCP/IP communication and dry contact function, making it easy to connect with the customer’s system. |
Touch Screen Control
Customers can monitor charging status and real-time alarms via a touch screen. |
| GENERAL | |
| Model | uXcel ultra -220V80A/16V60A |
| Topology | 6 pulse full bridge thyristor rectifier |
| Control | Microprocessor controlled system |
| Standars | IEC60146、IEC60439、IEC60725、IEC61000-6-2、IEC61000-6-4、IEC62040(-1,-2,-3) |
| Configuration | Parallel(One work, one standby) |
| ENVIRONMENT | |
| Operation temperature | 0 – 50℃ |
| Storage temperature | -20 to +70℃ |
| Relative humidity | < 95% ( no condensation of moisture ) |
| Altitude | 1000 m Max without derating |
| INPUT PARAMETERS | |
| Input isolation transformer | Galvanically isolated / Primary & Secondary earth screened |
| AC voltage and tolerance | 380VAC±10%, three-phase |
| Input frequency and tolerance | 50Hz/60Hz ±5% |
| Input protection | Input MCCB Thermic magnetic overcurrent protection,AC SPD |
| OUTPUT PARAMETERS | |
| Nominal output voltage | 220VDC/16VDC |
| Float voltage | 0-300V/0-24V adjustable |
| Boost voltage | 0-300V/0-24V adjustable |
| Voltage stability | ±1% in float mode, input within tolernce |
| Nominal output current | 80/60A |
| Output current adjustment | 0‐100% of Nominal Output Current |
| Output ripple | 1% RMS (with battery connected) |
| Mode of operation | constant voltage/constant current |
| Static voltage regulation | < 1% |
| Efficency | 88% |
| Filter | L-C Filter |
| Output breaker | DC1 battery MCCB,DC1 load MCCB,DC2 battery MCCB,Total load MCCB |
| Battery bank | Lead Acid or Nickel Cadmium vented or recombination |
| Boost voltage (V/C) | 2,35 lead acid battery 1,60 NiCd Battery (Depends on battery manufacturer recommendation) |
| Float voltage (V/C) | 2,25 lead acid battery 1,40 NiCd battery (Depends on battery manufacturer recommendation) |
| MECHANICAL PARAMETERS | |
| External protection | IP20, Cold rolled sheet |
| Panel thickness | Load Bearing: 2 mm, Non Load Bearing: 1.5 mm |
| Frame Colour | RAL7035 |
| Noise(dB ) | <50 dB |
| Cooling | Fan cooling |
| Cable Entry | Bottom |
| Dimensions | 1600H*1200W*800D(mm) |
| DISPLAY PANEL & MEASUREMENT | |
| Meter | DC1 voltage, DC2 voltage,Total voltage,DC1 current,DC1 current |
| Protection | Charger fault protection (DC overvoltage, DC overcurrent, Over temperature) |
| Alarm | Charger1 fault protection,Charger2 fault protection,BAT over temperature, Mains fault,DC1 overvoltage,DC1 undervoltage,DC2 overvoltage,DC2 undervoltage |
| Indication | LED lamp |
| Display | LCD display |
| OTHER FUNCTIONS | |
| Other funtions | |
| Battery temperature compensation | 3mV/cell, adjustable |
| Language | Customized |
| COMMUNICATION | |
| Communication | RS485, Modbus RTU |
| Dry contact | Charger fault |









Custom Dual-System Design
Dual Isolation Transformers
Voltage Adaptation
In Series Connection
Modbus & Dry Contact Functionality
Touch Screen Control